| Normal Thickness | Distance of any point on the upper surface of the veneer that deviates from the light weight straight ruler | |
| Veneer length 500 | Veneer length 1000 | |
| ≤15 | 2.0 | 4.0 |
| >15..≤25 | 1.5 | 3.0 |
| >25..≤60 | 1.0 | 2.0 |
| >60 | 1.0 | 1.5 |
Appearance Quality
| Item | Allowed Range |
| Swelling | Not Allowed |
| Cracking | |
| Dead Knot | |
| Foreign-body Adhering | |
| Insect Hole | |
| Rot | |
| Contamination | |
| Bruising | A few allowed, not effect in usage |
| Impression | |
| Color-odds and splash | |
| Patches per sq.m on surface | ≤3 |
GB Test Item— Before delivery Factory inspection
| Test Item | Unit | Standard | Test Method | |
| Vertical Bending Strength | Toward A | Mpa | ≥65 | GB/T2634—2008 Test Standard |
| Toward B | ≥65 | |||
| Vertical Bending modulus of elasticity | Toward A | Gpa | ≥8 | |
| Toward B | ≥8 | |||
| Compressibility (under 20MPa) | Toward C | % | ≤3 | |
| Intestine | ≥70 | |||
| Impact strength (side test) | Toward A | KJ/㎡ | ≥13 | |
| Toward B | ≥13 | |||
| Interlaminar shear strength | Mpa | ≥8 | ||
| Vertical electric strength (90 ℃ + 2 ℃) | KV/mm | ≥11 | ||
| Vertical electric strength (90 ℃ + 2 ℃) | KV | ≥50 | ||
| Performance density | g/cm³ | >1.1~1.2 | ||
| water content | % | ≤6 | ||
| Shrinkage after drying | Toward A | % | ≤0.3 | |
| Toward B | ≤0.3 | |||
| Toward thickness | ≤3 | |||
| Oil absorption | % | ≥8 | ||
By from -